C.BREAKER TMAX T7S 1000 FIXED THREE-POLE WITH FRONT TERMINALS AND LEVER OPERATING MECHANISM AND SOLID-STATE RELEASE IN AC PR232/P-LSI R 1000
- · Moulded Case Circuit Breaker
Specification
Number of auxiliary contacts as normally open contact : 0
Complete device with protection unit : Yes
DIN rail (top hat rail) mounting optional : No
Motor drive optional : No
Integrated earth fault protection : No
Overload release current setting : 400 – 1000 A
Suitable for DIN rail (top hat rail) mounting : No
With switched-off indicator : No
Motor drive integrated : No
Adjustment range short-term delayed short-circuit release : 600 – 10000 A
Adjustment range undelayed short-circuit release : 1500 – 12000 A
Type of electrical connection of main circuit : Bolt connection
Number of auxiliary contacts as change-over contact : 0
Rated voltage : 690 – 690 V
Number of poles : 3
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz : 50 kA
Rated permanent current Iu : 1000 A
Device construction : Built-in device fixed built-in technique
Number of auxiliary contacts as normally closed contact : 0
Type of control element : Toggle
Position of connection for main current circuit : Front side
Degree of protection (IP) : IP20